The V108 is a compact, 4 digit indicator (with alarms) that fits 1/8 DIN cutouts. It accepts temperature inputs from J, K, T, L, N, R, S, B, C and Platinel II type thermocouples and three-wire Platinum 100 Ohm (Pt100) RTDs. Process variables such as 4-20mA or ranges within -9.99 to 80mV can also be measured. Other thermocouple types such as D and E and custom curves can be configured at the factory. Voltage ranges from 0 to 10V can be measured with the optional (model SUB2-1V1) adapter.

Three programmable setpoint alarms can be field configured as rate of change, high or low; non-latching, latching or new. The new alarm indicates when a latched alarm has not been acknowledged

and the measured value crosses the setpoint trip level a second time. Alarm hysteresis (deadband) can be configured from 1 to 9999 process variable units. Each alarm has a programmable delay

up to 999.9 seconds. The alarms can be linked to either of two relay outputs. Alarms can be configured in combination (e.g. one or all three alarms linked to one or both relays) and will operate in fail-safe (e.g., normally energized) or non fail-safe modes. Additionally, the unit can be configured for password protection, limiting operator access to any or all functions. An alarm blocking function is also configurable to prevent alarm tripping during process or start-up. The unit also accepts wiring for remote alarm acknowledgment.

Thermocouples, three-wire RTDs and mV inputs can be accepted directly into the indicator. Current signals such as 4-20mA are input using a 2.49 Ohm shunt resistor, included with the indicator

and mounting hardware. Other shunt resistor values can be used to measure higher current levels, provided the produced signal is within the -9.99mV to 80mV input range. Similarly, voltage inputs such as 0-10V can be measured using the optional attenuator (model SUB2-1V1). The input can be scaled as desired for display. Offset and two point slope adjustments are fully programmable.

 

V108

FEATURES:

  • Eliminates Ground Loops

  • Easy Field Configurable Switch Selectable Input Ranges

  • Wide Ranging Zero and Span Adjustability (80%)

  • Protects Equipment with 600V Input-to- Output Isolation

  • Three Year Warranty

Application

The V108 is excellent for temperature and process variable measurement. The NEMA 4, front plug-in, panel mount indicatorfits standard 1/8 DIN cutouts.

The field configurable V108 makes an ideal standardized solution for a variety of temperature measurement and on-off control applications. For example, it can be used to control the heating and cooling elements in an oven or environmental control system

using two setpoints for high and low temperature limits. Similarly, a 4-20mA pressure signal can be monitored and the setpoints used to control or alarm the gas pressure or liquid level in a tank or vessel. Weight, flow, pressure, temperature, speed, position and

rate are just some of the process variables that can be accurately displayed and monitored with this flexible and effective unit.

Specifications

Display:

4 digit (-999 to 9999) with programmable

decimal, green or red, 15.9mm (0.6 In.)

high characters

 

Inputs:

See Table 1

 

Output:

Relay (isolated): 2A, 264VAC resistive.

Minimum 12Vdc, 100mA.

 

Accuracy:

+/-1°C or +/-0.25% of reading, whichever

is greater

 

Cold Junction Compensation:

>30:1 rejection of ambient temperature

change. Uses Instant Accuracy cold

junction sensing technology to

eliminate warm-up drift and respond

rapidly to ambient temperature changes.

 

Input Filtering:

Off to 999.9 seconds

 

 

 

Panel Sealing:

NEMA 4, or IP54 (EN60529)

 

EMC Compliance (CE Mark):

Emissions: EN50081-2

Immunity: EN50082-2

 

Temperature:

Operating: 0 to 55°C (32 to 131°F)

Storage: -30 to 75°C (-22 to 167°F)

 

Humidity

5 to 95%RH, non-condensing

 

Power:

Standard 100 to 240VAC, -15%, +10%,

48 to 62Hz, 5Wmax.

 

Agency Approvals:

  • cUL listed per standard UL508.

  • CE conformance per EMC directive 89/336/EEC, amended by 93/68/EEC and Low Voltage Directive 73/23/EEC, amended by 93/68/EEC.

 

Ordering Information

Specify:

1. Model Number:

  • V108 - ALGNVH (Green LEDs)

  • V108-ALRDVH (Red LEDs)

2. Accessories: (see Accessories)

3. Optional Factory Configuration, specify C620 with the desired configuration information.

Accessories

The VisiPak model V108 is shipped with mounting brackets, a 2.49 Ohm shunt

resistor and user manual. In addition, the following accessories are available: