Eurotherm
Invensys Operations Management
.

Miniature Temperature/Process Indicator - V116, V132

Shop Online

The VisiPak models V116 and V132 are compact, 4 digit indicators (with alarms) that fit 1/16 and 1/32 Din cutouts, respectively. They accept temperature inputs from J, K, T, L, N, R, S, C, B, and Platinell II type thermocouples and two-wire Platinum 100 Ohm (Pt100) RTDs. Process variables such as 4-20mA or ranges within -12 to 80mV can also be measured. Other thermocouples such as D and E types or custom curves can be configured at the factory. Voltages ranges up to 0-10V can be measured with the optional (model SUB2-1V1) adapter.

Three programmable setpoint alarms can be field configured as high or low, non-latching and high or low or new, latching alarms. The new alarm indicates the situation when a latched alarm has not been acknowledged and the measured value crosses the setpoint trip level for the second time. Alarm hysterisis (deadband) can be configured from 1 to 9999 process variable units.

The alarms can be linked to either the relay output or the digital I/O terminals. The digital I/O terminals can be configured to accept alarm acknowledgment input (e.g. remote push button). Or when configured as an output, those terminals will provide a TTL signal or drive an optional (model SUB2-1R7) relay. These alarm outputs can be configured in combination (e.g. one or all three alarms linked to the relay) and will operate in fail-safe (e.g. normally energized) or non-fail-safe modes. Additionally, the display can be configured for password protection, limiting access to any or all functions.An alarm blocking function is also configurable to prevent alarms from tripping during a system’s initialization or start-up.

Thermocouple, two-wire RTD and mV inputs can be directly input into the indicator. Current signals such as 4-20mA are input using the 2.49W shunt resistor, which is included with the indicator and mounting hardware. Other shunt resistors can be used to measure higher current levels as long as the signal produced is within the -12mV to 80mV input range. Similarly, voltage inputs such as 0-10V can be measured using the optional input adapter or voltage divider (model SUB2-1V1). The four-digit display (9999) can be configured to match the input signal range to the preferred engineering units. Offsets and two point slope adjustments are fully programmable to compensate for sensor variances.

Application

The V116 and V132 are excellent for temperature and process variable measurement especially when panel space is limited. Extremely compact and efficient, the NEMA 4X, plug-in from front, panel mount indicators can fit in the smallest enclosures or OEM panels.

V116

FEATURES:

  • Field Configurable Input for Thermocouple, RTD, mV, and 4-20mA Signals

  • Three Field Configurable Alarm Setpoint with One or Two Alarm Outputs

  • Bright Green 4 Digit (9999) LED Display, Programmable for Engineering Units

  • Combination Alarm Functions, Alarm Blocking and Programmable Latching/Non-latching

  • IP54 Front Panel with Tactile Front Panel Configuration Buttons

  • Wide Ranging Power Supply: 85 to 264VAC or 20 to 29V DC or AC

  • Three Year Warranty

The field configurable VisiPak indicators make an ideal standardized solution for a variety of temperature measurement and onoff control applications. For example, either the V116 or the V132 can be used to control the heating and cooling elements in an oven or environmental control system using two setpoints for high and

low temperature limits. Similarly, a 4-20mA pressure signal can be monitored and the setpoints can be used to control or alarm the

gas pressure or liquid level in a tank or vessel. Weight, flow, pressure, temperature, speed, position and rate are just some of the process variables that can be accurately displayed and monitored with these highly compact and effective units.

Specifications

Display:

4 digit (-999 to 9999) with programmable

decimal, green, 10mm (0.4 In.) high

characters

 

Inputs:

See Table 1

 

Output:

  • Relay (isolated): 2A, 264VAC resistive. Minimum 12V DC, 100mA.

  • Logic (non-isolated): 9VDC, 12mA. Can be used as alarm output or alarm acknowledge input.

 

Accuracy:

+/-1°C or +/-0.25% of reading, whichever

is greater

 

Cold Junction Compensation:

>30 to 1 rejection of ambient temperature

change. Uses Instant Accuracy cold

junction sensing technology to eliminate

warm-up drift and respond rapidly to

ambient temperature changes.

Input Filtering:

Off to 999.9 seconds

 

Panel Sealing:

NEMA 4X, or IP65 (EN60529)

 

EMC Compliance (CE Mark):

  • Emissions: EN50081-2

  • Immunity: EN50082-2

 

Temperature:

  • Operating: 0 to 55°C (32 to 131°F)

  • Storage: -30 to 75°C (-22 to 167°F)

 

Humidity:

5 to 95%RH, non-condensing

 

Power:

Standard 85 to 264VAC, 48 to 62Hz,

optional 20 to 29V DC or AC, 5 W max.

 

Agency Approvals:

  • cUL listed per standard UL508.

  • CE conformance per EMC directive 89/336/EEC, amended by 93/68/EEC and Low Voltage Directive 73/23/EEC, amended by 93/68/EEC.

 

Ordering Information

Specify:

1. Model Number:

  • V116-ALVH (65-264VAC powered) or

  • V116-ALVL (20-29VDC/AC powered) or

  • V132-ALVH (65-264VAC powered) or

  • V132-ALVL (20-29VDC/AC powered)

2. Accessories: (see Accessories)

3. Optional Factory Configuration, specify C620 with the desiredconfiguration information. 

Accessories

The VisiPak model V116 and V132 are shipped with mounting brackets,

2.49 Ohm shunt resistor and user manual. In addition, the following

accessories are available:

  • SUB2-1R7 External Relay

  • SUB2-1V10-10V Input Adapter

Get a Quote

» Indicates required fields

Request for Quote
Your Details
Company Details
*Leave State / Province Code  blank if not applicable*
Contact Details
Product Requirements

Get Support

Visit the Eurotherm Support site