|
Diagnostic LEDs The
Q126 is equipped with three front panel LEDs. The first is a dual function LED
labeled IN (INPUT) This green LED indicates AC power and input signal status.
Active AC power is indicated by an Protecting the Integrity of Industrial
Process Signals An Invensys Company illuminated LED. If this LED is off, check
line power and wiring connection. If the input signal is 7% above or below the
configured input range the green LED will flash at 8Hz or 4Hz, repectively.
Two red LEDs indicate the relay state for each setpoint. An
illuminated red LED indicates a tripped condition.
Output The Q126 is
equipped with two SPDT (form C) relays, rated at 120VAC or 28VDC at 5 amperes.
Each of these relays is independently controlled by the field configurable
setpoint and deadband.

Operation The field
configurable Q126 limit alarm setpoints can be configured for HI or LO,
failsafe or non-failsafe operation. Each of the setpoints has a respective HI
or LO deadband. In a tripped condition, the setpoint is exceeded and the
appropriate red LED will illuminate.
Dynamic Deadband LSI
circuitry in the Q126 prevents false trips by repeatedly sampling the input.
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted,
to qualify as a valid trip condition. Likewise, the input must fall outside the
deadband and remain there for 100 milliseconds to return the alarm to an
untripped condition. This effectively results in a dynamic deadband
based on time in addition to the normal deadband.
Configuration Unless
otherwise specified, the factory presets the Model Q126 as follows:
| Input: |
J Type |
| Range: |
0 to 350°C |
| Output: |
Dual, SPDT |
| Trip: |
A: HI, B: LO |
| Failsafe: |
No |
| Deadband: |
A, B: 0.25% |
|
|
For other I/O ranges, refer to Table 1 and reconfigure
switches SW1 and SW2 for the desired input type, range and function.
- With the module removed from the rail and not powered,
snap off the faceplate by lifting the right edge away from the heat sink. Note
the input switches (SW1 & SW2) are located under the face plate. Set
positions 1 through 3 on "SW1" and positions 1 through 8 on "SW2" for the
desired input and range. (see Table 1)
- Set positions 4 and 5 of the function switch
SW1 to ON (closed) for a HI trip setpoint or OFF (open) for a LO
trip setpoint (Figure 4).
- Set position 6 of function switch SW1 to ON
for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon
power failure).
- Set positions 7 and 8 of function switch "SW1" to upscale
or downscale burnout.
Calibration
- After configuring the DIP switches, connect the input to
a calibrated t/c source and apply power. Refer to the terminal wiring in the
Specifications section
- Starting Calibration: After applying power to the unit
all three LEDs will flash for approximately 10 seconds. Next, input the signal
level for Relay A setpoint, the green LED should be on. Press the
CAL button and hold for 4 seconds (until the red LED starts flashing) to enter
the calibration mode. The green LED should be on and the red Relay
A LED should now be flashing.
- Setpoint A: Input the desired trip level for
Relay A, if not already done, and push the CAL button. The green
and the red Relay A LED should be flashing. Note, the green LED
will stop flashing when the input drops below a high setpoint or rises above a
low setpoint.
- Deadband A: For minimum deadband (0.25%
approx.), press and hold the CAL button for 4 seconds. For high setpoints lower
the input level (green LED turns off) to the desired deadband point and push
the CAL button. For low setpoints increase the input level to the desired
deadband level and push the CAL button. The green LED should be on and the red
Relay B LED should be flashing.
- Setpoint B: Input the desired trip level for
Relay B, and push the CAL button. The green and the red Relay
B LED should be flashing.
- Deadband B: For minimum deadband (0.25%
approx.), press and hold the CAL button for 4 seconds. For high setpoints lower
the input level (green LED turns off) to the desired deadband point and push
the CAL button. For low setpoints increase the input level to the desired
deadband level and push the CAL button. The green LED should be on and both the
red LEDs should be flashing.
- Press the CAL button one final time to exit the
calibration mode. Check the setpoint and deadband to validate calibration.
|