|
Application DC input
four-wire transmitters are used to isolate and convert DC voltage or current
signals into proportional, standard industrial control signals such as-5/5V or
-10/10V. Typically an industrial control system such as a DCS or PLC requires
standard industrial control signals and isolation to ensure reliable strong
signals.
In most industrial process control or data acquisition
applications several different input sources, including voltages and currents
from various field instruments (e.g. level, flow, pressure and position
sensors), are common. Four-wire transmitters accept these field inputs and
provide the controller (DCS & PLC) the standard industrial signals they
require. The four-wire transmitter will increase the signal drive to high
impedance loads and may improve resolution of the process variable.
The 2000VAC isolation capability of the Q403 prevents ground
loops from causing errors in DC signals. Filtering and common mode rejection
are included to reduce susceptibility to Electro Magnetic Interference (EMI)
and Radio Frequency Interference (RFI). Isolation also provides protection from
high voltages and current spikes which may damage expensive Supervisory Control
And Data Acquisition (SCADA) equipment.
Operation The ActionI/Q
model Q403 operates as a fourwire transmitter; each channel derives its power
from an independent, transformer isolated, AC to DC power source (85 to
265VAC).
The Q403 has fixed input and output ranges. Standard input
and output ranges in Tables 1 & 2 are calibrated to rated accuracy. One
range per module; two channels per module, maximum. |
|
 Calibration
- To check calibration connect the input to a calibrated DC
source. Connect the output to a DC voltage or current meter and the input power
to an AC source (between 85 and 256 VAC) capable of providing up to 0.5
Amps.
- Set the calibrator to the specified minimum DC input
value and adjust the zero potentiometer for minimum (e.g.-10V) output.
- Set the calibrator to the specified maximum DC input
value and adjust the span potentiometer for maximum (e.g. +10V) output.
- Repeat steps 2 and 3 to validate calibration to the
output load.
Note: To maximize accuracy and thermal stability, final
calibration should be performed with the intended output load and the unit
should be mounted in the operating installation, allowing at least 1 hour for
warm up and thermal equilibrium of the system.
 |