The ActionI/Q model Q486 is a DIN rail mount,
RTD, thermocouple, mV or Ohm input signal conditioner with 1800V isolation
between input, output and power. The field configurable input and output offers
flexible, wide ranging capability for most temperature signal conditioning
applications.
The ActionI/Q model Q486 is a DIN rail mount,
RTD, thermocouple, mV or Ohm input signal conditioner with 1800V isolation
between input, output and power. The field configurable input and output offers
flexible, wide ranging capability for most temperature signal conditioning
applications.
An optional Microsoft Windows® based (PC)
program on CD ROM and serial port adapter cable are available (model C681) for
those who would prefer PC configuration capability. The Graphic User Interface
(GUI) program takes the place of setting DIP switches and using the push button
for ranging. The C681 GUI program can significantly speed configuration and an
input signal calibrator is not required for ranging since the values only need
to be typed in the program and down loaded.
INSTANT ACCURACY
ACCURACY TECHNOLOGY Instant Accuracy Technology is incorporated to
maximize accuracy and performance during warm up and during changes in ambient
temperature. This patented cold-junction compensation technique utilizes two
temperature sensors to measure the differential temperature near the terminal
block. Using heat transfer calculations with the measured differential
temperature and the known thermal conductivity of the PCB, we can determine the
terminal junction temperature with extreme accuracy. Even during unstable
thermal states such as start-up ambient temperature changes or
changing load or power, the Q486 performs extremely accurate thermocouple
temperature measurement.
The direct benefits of Instant Accuracy
include improved system performance and productivity due to reduced warm up
time, fewer temperature measurement errors and tighter process control for
higher quality. Finally and possibly most significantly, calibration can be
checked quickly and accurately without the effects of rapid ambient temperature
changes due to opening a control panel door. This often causes erroneous
readings and miscalibrations; a common cause of measurement errors.
TOUCHCAL
TECHNOLOGY TouchCAL technology allows easy field ranging for any of
the thermocouple or RTD input types. For example, the dip switch configured
range for the J type thermocouple is -210 to 760°C. Using a thermocouple
simulator as a reference, the model Q486 could be ranged for 0 to 50°C or 0
to 500°C by simply applying the desired minimum and maximum input levels
and pushing the range button to store the levels in non-volatile memory. The
output is ranged by applying an input signal to achieve an accurate output
level and pushing the range button. |