Q404-4
DC Input Isolator, Signal Splitter


TECHNICAL SPECIFICATION (Q404-4)
Input Range: 4-20mA
Impedance: >1MW (voltage inputs) , < 20W (current inputs)
Protection: withstands up to 24VDC (current input), 120VAC (voltageinput) without damage
Common Mode: 2000VAC, input to ground
Output Range: 4-20mA
Voltage Output Drive: 10mA (1000W min.)
Current Output Compliance: 15V (750W max.)
LED Indication Green LED indicates power on
Output Accuracy < +0.1% of full-scale input typical,
< +0.2% maximum @23C including linearity, repeatability and hysteresis
Adjustability Front accessed 10 turn, for adjustmetn of r zero and span
Stability < 0.025%/C of full-scale maximum for full-scale and zero
Isolation > 2000VAC between input and output and channel to channel
EMC Compliance (CE Mark)
Emmissions: EN50081-1
Immunity: EN50082-2
Safety: EN50178
Response Time 25mSec typical (10 to 90%)
Power 10.8 to 26.4VDC, 2W
Temperature Operating: -5 to 60°C (23 to 140°F)
Storage: -40 to 80°C (-40 to 176°F)
Humidity (non-condensing)
Operating: 15 to 90% (@45°C)
Soak: 90% for 24 hours (@60°C)
Wire Terminal Socketed screw terminals for 12-22 AWG
Agency Approvals UL recognized per standard UL508 (File No. E99775). CSA certified per standard C22.2 No. 0-M91 and 142-M1987 (File No. LR42272-84). CE conformance per EMC directive 89/336/EEC and Low Voltage 73/23/EEC.

Operation
The ActionI/Q model Q404 operates as a fourwire transmitter; each channel derives its power from an independent, transformer isolated, DC to DC power source (10.8 to 26.4VDC). Typically a 12 or 24VDC source is used for power.

The Q404 has fixed input and output ranges. Standard input and output ranges in Table 1 are calibrated to rated accuracy. Units are configured for one range per module and one or two channels per module.

Note: To maximize accuracy and thermal stability, final calibration should be performed with the intended output load and the unit should be mounted in the operating installation, allowing at least 1 hour for warm up and thermal equilibrium of the system.

Calibration
  1. To check calibration, connect the input to a calibrated DC source. Connect the output to a DC voltage or current meter and the input power to DC source (10.8 to 26.4VDC) capable of providing up to 0.5 Amps.
  2. Set the calibrator to the specified minimum DC input value and adjust the zero potentiometer for minimum (e.g. 4mA) output.
  3. Set the calibrator to the specified maximum DC input value and adjust the span potentiometer for maximum (e.g. 20mA) output.
  4. Repeat steps 2 and 3 to validate calibration to the output load.