AP1680/AP1690
DC Input, Field
Configurable Limit Alarms |
TECHNICAL SPECIFICATION ( AP1680-2000/AP1690-2000)
|
| Input |
Voltage Input: |
|
|
|
Range: |
|
100mV to 200V AC |
|
Impedance: |
|
>100K Ohmns |
|
Overvoltage: |
|
300VAC, max |
|
|
|
|
| Current Input: |
|
|
| Full Scale Range: |
|
10mA to
100mA |
|
Impedance: |
|
20 Ohms, typical |
|
Overcurrent: |
|
200mA, max |
|
Frequency range |
|
DC 40-400Hz,
factory calibrated at 60Hz |
| Common Mode (Input toGround): |
|
1000V,
max |
|
LED Indications |
|
|
|
Input Range (Green) |
|
>100% input: 8Hz flash |
|
|
|
<0%
input: 4Hz flash |
| |
Setpoint (Red) |
|
Tripped: Solid red |
|
|
|
Safe: Off |
| Limit Differential |
|
|
|
|
|
|
.25% to
50% of span |
|
|
|
|
| Response Time: |
|
|
|
|
Dynamic Deadband: |
|
Relay status will change
when proper setpoint/process condition exists uninterrupted
for 100ms |
| Normal Mode (analog filtering) |
|
<250ms,
(10-90%) |
| Setpoint: |
|
|
|
|
Effectivity: |
|
Setpoints
are adjustable over 100% of the selected input span. |
|
Repeatability (constant temp): |
>50mV/5mA: .1% of full
scale |
|
|
|
<50mV/5mA: .2% of full scale |
| Stability |
|
|
|
| Line Voltage: |
|
± .01%,
max. |
|
Temperature: |
|
± .025% of full scale/°C,
max. |
| Common
Mode Rejection |
|
|
| |
DC
to 60Hz: |
|
120dB |
| Isolation |
|
|
1000 VDC
between contacts, input and power |
| ESD
Susceptibility |
|
Meets IEC 801-2, Level 2
(4KV) |
| Humidity (Non-Condensing) |
|
|
|
Operating: |
|
15 to 95% (@ 45°C) |
|
Soak: |
|
90% for 24
hours (@ 45°C) |
| Temperature Range |
|
|
|
Operating: |
|
-15 to
60°C (5 to 140°F) |
|
Storage: |
|
-25 to 70°C (-13 to
158°F) |
| Power |
Consumption: |
|
2W typical,
5W max |
|
Standard: |
|
selectable 120/240VAC,
±10%, 50-60Hz |
|
Optional: |
|
9 to 30VDC,
inverter isolated |
| Weight |
|
|
.64 lbs |
| Agency Approvals |
|
CSA
certified per standard C22.2, No. M1982. |
|
|
|
UL recognized per standard
UL508. |
|
Diagnostic LED
Models AP1680-2000 and AP1690-2000 are equipped with dual
function diagnostic LED. The green center LED indicates
line power and input signal status. Active line power is
indicated by an illuminated LED. If the center LED is off,
check line power and the wiring connection. If the input
signal is above 100% full scale, the LED will flash at
approximately 8Hz. Below 0%, the flash rate is
approximately 4Hz.
Operation
The field
configurable AP1680 and AP1690 limit alarm setpoints can be
configured for HI, LO, latching or failsafe trip operation.
Non-latching HI and LO setpoints have respective HI and LO
deadbands. In a tripped condition, the setpoint is exceeded
and the appropriate red LED will illuminate. The trip will
reset only when the process falls below the HI deadband or
rise above the LO deadband. To reset a latched setpoint the
signal must be in the safe region and the line power turned
off for at least 5 seconds. For proper deadband operation,
a HI setpoint must always be set above a Lo setpoint.
|
|
Calibration
Note: To maximize thermal stability, final calibration
should be performed in the operating installation, allowing
approximately 1 - 2 hours for warmup and thermal
equilibrium of the system.
Setpoint: Set deadband at
its minimum (about 20 turns Counter Clockwise) before
adjusting the setpoint. With the specified trip voltage or
current input applied, adjust setpoint until the relay
trips. For HI trip calibration, start with the setpoint
above the desired trip. For LO trip calibration, start
below the desired trip.
Deadband: Set deadband to
its minimum (about 20 turns Counter Clockwise). Set
setpoint to desired trip. Adjust voltage/current input
until relay trips. Readjust deadband to 50% (20 turns CW).
Set voltage/current input to desired deadband position.
Slowly adjust deadband until relay untrips. |
|