AP4380-2000/AP4380-2001 DC Input, Field Configurable
Isolator |
TECHNICAL SPECIFICATION ( AP4380-2000/AP4380-2001)
|
| Input |
Full Scale Range: |
|
Voltage Input
(field configurable) |
|
-2000: |
|
10mV to 100V |
|
-2001: |
|
10mV to 200V |
|
Impedance: |
|
>100K
Ohms |
|
Overvoltage: |
|
Intermittent, 400Vrms |
|
|
|
Continous,
264 Vrms |
| Current Input (field configurable) |
|
|
|
Full Scale Range: |
|
1mA to
100mA |
|
Impedance: |
|
20 Ohms, typical |
|
Overcurrent: |
|
170mA RMS,
max |
|
Overvoltage: |
|
60VDC |
| Common Mode (Input toGround): |
|
1500VDC,
max |
|
Zero Turn-Up: |
|
50% of full scale range |
|
Span Turn-Down: |
|
50% of full
scale range |
| Output |
Voltage Output |
|
|
|
Output: |
|
0-5V,
0-10V |
|
Drive: |
|
10mA, max (1K Ohms min. @
10V) |
|
Current Output |
|
|
|
Output: |
|
0-1mA, 4-20mA |
|
Compliance: |
|
0-1mA: 10V,
max. (10K Ohms, max) |
|
|
|
4-20mA: 20V, max. (1K Ohms,
max) |
| LED Indication (green) |
|
|
|
Input Range |
|
>110% input: 8Hz flash |
|
|
|
<0%
input: 4Hz flash |
| Accuracy
Including Linearity Hysteresis |
|
|
<20mV/2mA: |
|
±0.35% of full scale, typical, 0.5%, max |
|
>20mV/2mA: |
|
±0.1% of full scale,
typical, 0.2%, max |
| Response Time (10-90%) |
|
200 mSec.,
typical |
| Stability
(Temp) |
|
±0.025% of full
scale/°C, typical, |
|
|
|
±0.05%/°C, max. |
| CMRR |
DC
to 60Hz: |
|
120dB |
| Isolation |
|
|
500 VDC
between input, output and power |
| ESD
Susceptibility |
|
Meets IEC 801-2, Level 2
(4KV) |
| Humidity (Non-Condensing) |
|
|
|
Operating: |
|
15 to 95% (@ 45°C) |
|
Soak: |
|
90% for 24
hours (@ 45°C) |
| Temperature Range |
|
|
|
Operating: |
|
-15 to
60°C (5 to 140°F) |
|
Storage: |
|
-25 to 70°C (-13 to
158°F) |
| Power |
Consumption: |
|
3W typical,
5W max |
|
Standard: |
|
selectable 120/240VAC,
±10%, 50-60Hz |
|
Optional: |
|
9 to 30VDC,
inverter isolated |
| Weight |
|
|
AP4380 .60lbs |
| Agency Approvals |
|
CSA
certified per standard C22.2, No. M1982. |
|
|
|
UL recognized per standard
UL508. |
|
Diagnostic LED The
AP4380 is equipped with a dual function LED signal monitor. The green,
top-mounted LED indicates line power and input signal status. Active line power
is indicated by an illuminated LED. If the input signal is 10% more than full
scale range, the LED will flash at 8Hz. Below 0%, the flash rate is 4Hz.
Application The factory
presets the 4380-2000 input and output to 4-20mA, as shown in Figure 1. The
4380-2001 is preset to 0/200V input and 4/20mA output. The supply power is
configured for 120 VAC operation. For other I/O ranges, remove the four base
screws and case to access the I/O card. |
|
Calibration
- Connect the input to a calibrated DC voltage or current
source and apply power. Wait 1 hour for thermal stability before monitoring the
voltage/ current output. Refer to PIN CONNECTIONS.
- Set the calibrator to the desired minimum input and
adjust the Zero, 20-turn, potentiometer for desired minimum output.
- Set the calibrator to the desired maximum input and
adjust the Span, 20-turn, potentiometer for desired maximum output.
- Repeat steps 2 and 3 for best accuracy.
|
|