AP4382 DC Input, Bipolar Output, Field Configurable
Isolator |
TECHNICAL SPECIFICATION ( AP4382) |
| Input |
|
|
Voltage Input
(field configurable) |
|
Full Scale Range: |
|
10mV to 100V |
|
Impedance: |
|
>100K
Ohms |
|
Overvoltage: |
|
400 Vrms,
max (Intermittent) |
|
|
|
264 Vrms, max (Continous) |
| Current Input (field configurable) |
|
|
|
Full Scale Range: |
|
1mA to 100mA |
|
Impedance: |
|
20 Ohms,
typical |
|
Overcurrent: |
|
170mA rms, max |
|
Overvoltage: |
|
60VDC |
| Common
Mode (Input to Ground): |
|
1500VDC, max |
| Zero and Span Range |
|
|
|
Zero Turn-Up: |
|
0 to 50% of full scale
range |
|
Span Turn-Down: |
|
100 to 50%
of full scale range |
| Output |
Voltage Output |
|
|
|
Output: |
|
-10 to 10V,
-5 to 5V |
|
Impedance: |
|
<10 Ohms |
|
Drive: |
|
10mA, max
(1K Ohms min. @ 10V) |
| LED
Indication (green) |
|
|
|
Input Range >110% input: |
|
8Hz
flash |
|
<0% input: |
|
4Hz flash |
| Accuracy Including Linearity, Hysteresis |
|
|
<20mV/2mA: |
|
±0.35% of full scale,
typical, 0.5%, max |
|
>20mV/2mA: |
|
±0.1%
of full scale, typical, 0.2%, max |
| Response
Time (10-90%) |
|
200 mSec., typical |
| Stability (Temperature) |
|
±0.025% of full scale/°C,
typical, ±0.05%/°C, max |
| CMRR |
DC
to 60Hz: |
|
120dB |
| Isolation (Input to Output) |
|
1500 VDC
between input, output and power |
| ESD
Susceptibility |
|
Meets IEC 801-2, Level 2
(4KV) |
| Humidity (Non-Condensing) |
|
|
|
Operating: |
|
15 to 95% (@ 45°C) |
|
Soak: |
|
90% for 24
hours (@ 65°C) |
| Temperature Range |
|
|
|
Operating: |
|
-15 to
60°C (5 to 140°F) |
|
Storage: |
|
-25 to 70°C (-13 to
158°F) |
| Power |
Consumption: |
|
3W typical,
5W max |
|
Standard: |
|
selectable 120/240VAC,
±10%, 50-60Hz |
|
Optional: |
|
9 to 30VDC,
inverter isolated |
| Weight |
|
|
0.60lbs |
| Agency Approvals |
|
CSA
certified per standard C22.2, No. M1982 (File No.LR42272-54). |
|
|
|
UL recognized per standard
UL508 (File No. E150323). |
|
Diagnostic LED The
AP4382 is equipped with a dual function LED signal monitor. The green,
top-mounted LED indicates line power and input signal status. Active line power
is indicated by an illuminated LED. If the input signal is 10% above the full
scale range, the LED will flash at 8Hz. Below 0%, the flash rate is 4Hz.
Configuration The
factory preset input is 4-20mA and the output is -10 to 10V, as shown in Figure
1. The supply power is configured for 120 VAC operation. For other I/O ranges,
remove the four base screws and case to access the I/O card.
WARNING: Do not change switch settings with power
applied. Severe damage will result! |
|
Calibration
- Connect the input to a calibrated DC voltage or current
source and apply power. Wait 1 hour for thermal stability before monitoring the
voltage/ current output. Refer to PIN CONNECTIONS.
- Set the calibrator to the desired minimum input and
adjust the Zero, 20-turn, potentiometer for desired minimum output.
- Set the calibrator to the desired maximum input and
adjust the Span, 20-turn, potentiometer for desired maximum output.
- Repeat steps 2 and 3 for best accuracy.
|
|