|
Diagnostic LEDs The
G108 is equipped with three front panel LEDs. The green LED is a dual function
LED labeled INPUT. This LED indicates line power and input signal status.
Active DC power is indicated by an illuminated LED. If this LED is off, check
DC power and wiring connection. If the input signal is more than 110% of the
full scale range, the LED will flash at 8 Hz. Below 0%, the flash rate is 4
Hz.
Two red LEDs indicate the relay state for each setpoint. An
illuminated red LED indicates the tripped condition.
Output The G108 is
equipped with two SPDT (form C) relays, rated at 120VAC or 28VDC at 5 amperes.
Each of these relays is independently controlled by the field configurable
setpoint and deadband.
Operation The field
configurable G108 limit alarm setpoints can be configured for HI or LO,
failsafe or non-failsafe operation. Each of the setpoints has a respective HI
or LO deadband. In a tripped condition, the setpoint is exceeded and the
appropriate red LED will illuminate. The trip will reset only when the process
falls below the HI deadband or rises above the low deadband (see Figure 1). For
proper deadband operation, the HI setpoint must always be set above the LO
setpoint. In failsafe operation, the relay is energized when the process is
below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In
the failsafe mode, a power failure results in an alarm state output.

Dynamic Deadband LSI
circuitry in the G108 prevents false trips by repeatedly sampling the input.
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted,
to qualify as a valid trip condition. Likewise, the input must fall outside the
deadband and remain there for 100 milliseconds to return the alarm to an
untripped condition. This effectively results in a dynamic deadband
based on time in addition to the normal deadband.
Configuration Unless
otherwise specified, the factory presets the Model G108 as follows:
| Input: |
Current |
| Range: |
0-20mA |
| Output: |
Dual, SPDT |
| Trip: |
A:HI, B:LO |
| Failsafe: |
No |
| Deadband: |
A, B: 0.25% |
|
|
The DC power input accepts any DC source between 9 and 30V,
typically a 12V or 24VDC source is used (see Accessories).
For other I/O ranges, refer to Table 1 and Figure 4.
Reconfigure switch SW1 for the desired input type, range and function.
- With DC power off, set position 9 and 10 of SW1 for
current or voltage (see Table 1).
- Set position 1 through position 4 of input range switch
SW1 for the desired input range (see Table 1).
- Set position 5 of input range switch SW1 to
ON for unipolar (e.g. zero based, 0-20mA) range or OFF for bipolar (e.g. -100%
offset, -20 to 20mA) range (see Figure 4).
- Set position 6 and 7 of input range switch
SW1 to ON for a HI trip setpoint or OFF for a LO trip setpoint (see
Figure 4).
- Set position 8 of input range switch SW1 to
ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips
upon power failure).
Calibration
- After configuring the DIP switches, connect the input to
a calibrated DC source and apply power. Refer to the terminal wiring (Figure
7).
- Setpoint: set deadband at its minimum (fully counter
clockwise) before adjusting the setpoint. With the desired trip voltage or
current input applied, adjust setpoint until the relay trips. For HI trip
calibration, start with the setpoint above the desired trip (full clockwise).
For LO trip calibration, start below the desired trip (full counter
clockwise).
- Deadband: Set deadband to its minimum (fully counter
clockwise). Set the setpoint to desired trip. Adjust voltage/current input
until relay trips. Readjust deadband to 5% (fully clockwise). Set
voltage/current input signal to desired deadband position. Slowly adjust
deadband until relay untrips.

|