|
Diagnostic LEDs The
G118 is equipped with three front panel LEDs. The first is a dual function LED
labeled IN (input). This green LED indicates line power and input signal
status. Active DC power is indicated by an illuminated LED. If this LED is off,
check DC power and wiring connection. If the input signal is more than 110% of
full scale, the LED will flash at 8 Hz. Below -10%, the flash rate is 4 Hz.
Two red LEDs indicate the relay state for each setpoint. An
illuminated red LED indicates the tripped condition.
Output The G118 is
equipped with two SPDT (form C) relays, rated at 120VAC or 28VDC at 5 amperes.
Each of these relays is independently controlled by the field configurable
setpoint and deadband.
Operation The field
configurable G118 limit alarm setpoints can be configured for HI or LO,
failsafe or non-failsafe operation. Each of the setpoints has a respective HI
or LO deadband. In a tripped condition, the setpoint is exceeded and the
appropriate red LED will illuminate. The trip will reset only when the process
falls below the HI deadband or rises above the LO deadband (see Figure 1). For
proper deadband operation the HI setpoint must always be set above the LO
setpoint.
In failsafe operation, the relay is energized when the
process is below the HI setpoint or above the LO setpoint (opposite for
nonfailsafe). In the failsafe mode, a power failure results in an alarm state
output.
Dynamic Deadband LSI
circuitry in the G118 prevents false trips by repeatedly sampling the input.
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted,
to qualify as a valid trip condition. Likewise, the input must fall outside the
deadband and remain there for 100 milliseconds to return the alarm to an
untripped condition. This effectively results in a dynamic deadband
based on time in addition to the normal deadband.
Configuration Unless
otherwise specified, the factory presets the Model G118 as follows:
| Input: |
Platinum (100W) |
| Range: |
0 to 250°C |
| Output: |
Dual, SPDT |
| Trip: |
A:HI, B:LO |
| Failsafe: |
No |
| Deadband: |
A, B: 1.0% |
|
|
The DC power input accepts any DC source between 9 and 30V;
typically a 12V or 24VDC source is used (see Accessories).
For other I/O ranges, refer to Tables 1 through 3 and
reconfigure switches SW1 and SW2 for the desired input type, range and
function.
- With DC power off, position input switches 1 through 6 on
SW2 for RTD type (see Table 1).
- Set position 1 through position 4 of input range switch
SW1 for the desired RTD type and input temperature range (Table
3).
- Set position 5 and 6 of input range switch
SW1 to ON for a HI trip setpoint or OFF for a LO trip setpoint
(Figure 4).
- Set position 7 of input range switch SW1 to
ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips
upon power failure).
Calibration
- After configuring the DIP switches, connect the input to
a calibrated RTD source or a resistance decade box and apply power. (Figure
6).
- Setpoint Calibration: Before adjusting the setpoint,
adjust deadband pot to its minimum (20 turns counter clockwise). With the
desired trip RTD resistance input applied, adjust setpoint pot until the relay
trips. For HI trip calibration, start with the setpoint pot above the desired
trip (20 turns clockwise). For LO trip calibration, start with the setpoint pot
below the desired trip (20 turns counter clockwise).
- Deadband Calibration: Set deadband pot to its minimum (20
turns counter clockwise). Adjust the setpoint pot to desired trip. Adjust RTD
resistance input until relay trips. Readjust deadband pots to 5% (20 turns
clockwise). Set RTD resistance input to desired deadband position. Slowly
adjust deadband (counter clockwise) until relay untrips.
Relay Protection and EMI
SuppressionWhen switching inductive loads, maximum relay life and
transient EMI suppression is achieved using external protection (see Figures 2
and 3). Place all protection devices directly across the load and minimize all
lead lengths. For AC inductive loads, place a properly-rated MOV across the
load in parallel with a series RC snubber. Use a 0.01 to 0.1mF pulse film
capacitor (foil polypropylene recommended) of sufficient voltage, and a 47W,
1/2W carbon resistor. For DC inductive loads, place a diode across the load
(PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode
(the RC snubber is an optional enhancement). |