|
Diagnostic LEDs The
G128 is equipped with three front panel LEDs. The first is a dual function LED
labeled INPUT. This green LED indicates DC power and input signal status.
Active DC power is indicated by an illuminated LED. If this LED is off, check
line power and wiring connection. If the input signal is more than 110% of the
full scale range, the LED will flash at 8 Hz. Below -10%, the flash rate is 4
Hz.
Two red LEDs indicate the relay state for each
setpoint. An illuminated red LED indicates the tripped condition.
Output The G128 is
equipped with two SPDT (form C) relays, rated at 120VAC or 28VDC at 5 amperes.
Each of these relays is independently controlled by the field configurable set
point and deadband.
Operation The field
configurable G128 limit alarm setpoints can be configured for HI or LO,
failsafe or non-failsafe operation. Each of the setpoints has a respective HI
or LO deadband. In a tripped condition, the setpoint is exceeded and the
appropriate red LED will illuminate. The trip will reset only when the process
falls below the HI deadband or rises above the low deadband (see Figure 1). For
proper deadband operation, the HI setpoint must always be set above the LO
setpoint.
In failsafe operation, the relay is energized when the
process is below the HI setpoint or above the LO setpoint (opposite for
non-failsafe). In the failsafe mode, a power failure results in an alarm state
output.
Dynamic Deadband LSI
circuitry in the G128 prevents false trips by repeatedly sampling the input.
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted,
to qualify as a valid trip condition. Likewise, the input must fall outside the
deadband and remain there for 100 milliseconds to return the alarm to an
untripped condition. This effectively results in a dynamic deadband
based on time in addition to the normal deadband.
Configuration Unless
otherwise specified, the factory presets the Model G128 as follows:
| Input: |
J Type |
| Range: |
0 to 350°C |
| Output: |
Dual, SPDT |
| Trip: |
A: HI, B: LO |
| Failsafe: |
No |
| Deadband: |
A, B: 0.25% |
|
|
The DC power input accepts any DC source between 9 and 30V,
typically a 12V or 24VDC source is used (see Accessories).
For other I/O ranges, refer to Table 1 and reconfigure
switches SW1 and SW2 for the desired input type, range and function.
- With DC power off, position switch SW1-1, 2, 3 and SW2-1
through 6 for the desired input range (Table 1).
- Set positions 4 and 5 of function switch SW1
to ON for a HI trip setpoint or OFF for a LO trip setpoint (Figure 4).
- Set position 6 of function switch SW1 to ON
for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon
power failure).
- Set positions 7 and 8 of function switch "SW1" to upscale
or downscale burn-out.
Calibration
- After configuring the DIP switches, connect the input to
a calibrated TC source and apply power. Refer to the terminal wiring (Figure
5).
- Setpoint: set deadband at its minimum (20 turns counter
clockwise) before adjusting the setpoint. With the desired trip thermocouple
millivolt input applied, adjust setpoint until the relay trips. For HI trip
calibration, start with the setpoint above the desired trip (20 turns
clockwise). For LO trip calibration, start below the desired trip (full counter
clockwise).
- Deadband: Set deadband to its minimum (20 turns counter
clockwise). Set the setpoint to desired trip. Adjust thermocouple millivolt
input until relay trips. Readjust deadband to 5% (20 turns clockwise). Set
voltage/current input to desired deadband position. Slowly adjust deadband
until relay untrips
Relay Protection and EMI
Supression When switching inductive loads, maximum relay life and
transient EMI suppression is achieved using external protection (see Figures 2
and 3). Place all protection devices directly across the load and minimize all
lead lengths. For AC inductive loads, place a properly-rated MOV across the
load in parallel with a series RC snubber. Use a 0.01 to 0.1mF pulse film
capacitor (foil polypropylene recommended) of sufficient voltage, and a 47W,
1/2W carbon resistor. For DC inductive loads, place a diode across the load
(PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode
(the RC snubber is an optional enhancement). |