G448 Bridge Input Field Configurable Signal
Conditioner |
TECHNICAL SPECIFICATION (G448) |
| Input Voltage |
Full Scale Range: |
|
10mV to
±200mV |
|
Impedance: |
|
>1M Ohms |
|
Overvoltage: |
|
intermittent
400V, max.; |
|
|
continuous
264V, max. |
| Common Mode (Input to Ground) |
|
1800VDC, max. |
|
Zero Turn-Up: |
|
50% of full
scale range |
|
Span Turn-Down: |
|
50% of full scale range |
|
Operation: |
|
direct or
reverse acting |
| Output Voltage |
Output: |
|
0-5V, 0-10V |
|
Impedance: |
|
<10
Ohms |
|
Drive: |
|
10mA, max. (1K Ohms, min. @
10V) |
|
Current Output: |
|
0-1mA,
0-20mA, 4-20mA |
|
Impedance: |
|
>100K Ohms |
|
Compliance: |
|
0-1mA; 7.5V,
max.(7.5K Ohms, max.) |
|
|
|
0-20mA; 12V, max. (600 Ohms,
max.) |
|
|
|
4-20mA; 12V,
max. (600 Ohms, max.) |
| Bridge
Excitation |
|
1 to 10VDC, 120mA max. |
| Accuracy Including Linearity, Hysteresis |
±0.1%
typical, ±0.2% maximum of selected input range at 25°C. |
| Stability |
|
±0.025%/°C typical,
0.05%/°C maximum, of selected full scale input range. |
| Output Noise (maximum) |
|
0.1% of
span, rms, or 10mV whichever is greater. |
| Response
Time (10 to 90%) |
|
<200mSec., typical. |
| CMRR |
DC to 60Hz: |
|
>120dB, >100dB for 0 -1mA range |
| Isolation |
|
|
1800VDC between input, output
and power. |
| EMC Compliance (CE Mark) |
|
|
|
Emissions: |
|
EN50081-1 |
|
Immunity: |
|
EN50082-2 |
|
Safety: |
|
EN50178 |
| LED Indication (green) |
|
Input Range
(approx.) |
|
|
|
>110% input: 8Hz flash |
|
|
|
<0%
input: 4Hz flash |
| Humidity
(Non-Condensing) |
|
|
|
Operating: |
|
15 to 95% @
45°C |
|
Soak: |
|
90% for 24 hours @
65°C |
| Temperature Range |
|
|
|
Operating: |
|
0 to 55°C (32 to
131°F) |
|
Storage: |
|
-25 to
70°C (-13 to 158°F) |
| Power |
Consumption: |
|
2.5W typical (one 350 Ohm
bridge), |
|
|
|
4W max.
(four 350 Ohm bridges). |
|
Range: |
|
18 to 30VDC |
| Weight |
|
|
0.54
lbs. |
| Wire
Terminations |
|
Screw terminals for 12-22
AWG |
| Agency Approvals |
|
CSA
certified per standard C22.2, No. 0-M91 and 142-M1987 (File No. LR42272). |
|
|
|
UL recognized per standard
UL508 (File No.E99775). |
|
|
|
CE
Conformance per EMC directive 89/336/EEC and low voltage 73/23/EEC. |
|
Diagnostic LED The G448
is equipped with a dual function LED signal monitor. The green, front mounted
LED indicates both DC power and input signal status. Active DC power is
indicated by an illuminated LED. If the input signal is more than 110% of the
full scale range, the LED will flash at 8Hz. Below -10%, the flash rate is
4Hz.
Configuration The G448
has 11 input range switch settings. Trim potentiometers allow 50% input zero
and span adjustablity within each of the 11 full-scale, input ranges.
For example, the 200mV switch setting in Table 1 configures
the input for a 0 to 200mV range. Since the span can be contracted by 50%, this
enables an input span as narrow as 100mV of the range, or 50%. This span can be
positioned anywhere within the 0-200mV range with a zero off-set as large as
50% of the full scale range (e.g. 100 to 200mV input).
Unless otherwise specified, the factory presets the Model
G448 as follows:
| Input Setting: |
0 to 50mV |
| Input Range: |
0 to 30mV (3mV/V) |
| Excitation: |
10V |
| Operation: |
Direct |
| Output: |
4 to 20mA |
|
|
The DC power input accepts any DC source between 18 and 30V,
typically a 24VDC source is used (see Accessories).
For other I/O ranges refer to Tables 1 through 4 and
reconfigure switches SW1 and SW2 for the desired input range, function,
excitation and output range. Calibration
- After configuring the DIP switches, connect the input to
a calibrated millivolt source. Connect the output to the device (or a load
equivalent to the device) and apply power. (see Wiring Diagram, Figure 2 or
3).
- Set the calibrator to the desired minimum and adjust the
zero potentiometer for the desired minimum output.
- Set the calibrator to the desired maximum and adjust the
span potentiometer for the desired maximum output.
- Repeat steps 2 and 3, if necessary for best
accuracy.
|
|