G468 AC Input Field Configurable Isolator |
TECHNICAL SPECIFICATION (G468) |
| Inputs Voltage |
Ranges: |
|
100mV to
250VAC |
|
Impedance: |
|
>100K Ohms |
|
Overvoltage: |
|
300VAC |
|
Current Ranges: |
|
10mA to
100mA AC |
|
Impedance: |
|
20 Ohms, typical |
|
Overcurrent: |
|
200mAAC |
|
Overvoltage: |
|
60V peak |
|
Frequency Range: |
|
DC to 400Hz,
factory calibrated at 60Hz |
| Common Mode(Input to Ground): |
|
1800VDC, max. |
|
Zero and Span Range: |
|
Zero
Turn-Up: 50% of full scale range |
|
|
|
Span Turn-Down: 50% of full
scale range |
| Output Voltage |
Output: |
|
0-5V,
0-10V |
|
Source Impedance: |
|
<10 Ohms |
|
Drive: |
|
10mA, max.
(1K Ohms, min. @ 10V) |
|
Current Output: |
|
0-1mA, 0-20mA, 4-20mA |
|
Source Impedance: |
|
>100K
Ohms |
|
Compliance: |
|
0-1mA; 7.5V, max. (7.5K Ohms,
max.) |
|
|
|
0-20mA; 12V,
max. (600 Ohms, max.) |
|
|
4-20mA; 12V, max. (600 Ohms,
max.) |
| LED Indicator (green) |
|
8Hz flash
when input is 110% of full scale range |
|
|
|
4Hz flash when input is 10%
below full scale range |
| Accuracy Including Linearity, Hysteresis |
+0.1% of
span, typical |
|
|
|
+0.5% of span, maximum |
| Stability |
|
|
+0.025%/°C of selected input span, typical. |
| Response
Time (10 to 90%) |
|
250mSec., typical. |
| CMRR |
DC to 60Hz: |
|
120dB |
| Isolation |
|
|
1800VDC between input, output
and power. |
| EMC Compliance (CE Mark) |
|
|
|
Emmissions: |
|
EN50081-1 |
|
Immunity: |
|
EN50082-2 |
|
Safety: |
|
EN50178 |
| Humidity (Non-Condensing) |
|
|
|
Operating: |
|
15 to 95% @ 45°C |
|
Soak: |
|
90% for 24
hours @ 65°C |
| Temperature Range |
|
|
|
Operating: |
|
0 to
55°C (32 to 131°F) |
|
Storage: |
|
-25 to 70°C (-13 to
158°F) |
| Power |
Consumption: |
|
1.5W
typical, 2.5W max. |
|
Range: |
|
9 to 30VDC |
| Wire Terminations |
|
Screw
terminals for 12-22 AWG |
| Weight |
|
|
0.48 lbs. |
| Agency Approvals |
|
CSA
certified per standard C22.2, No. 0-M91 and 142-M1987 (File No. LR42272). |
|
|
|
UL recognized per standard
UL508 (File No.E99775). |
|
|
|
CE
Compliance per EMC directive 89/336/EEC and Low Voltage 73/23/EEC. |
|
Diagnostic LED The G468
is equipped with a dual function LED signal monitor. The green, front mounted
LED indicates both DC power and input signal status. Active DC power is
indicated by an illuminated LED. If the input signal is more than 110% of the
full scale range, the LED will flash at 8Hz. Below -10%, the flash rate is
4Hz.
Configuration The G468
has 15 input range switch settings. Trim potentiometers allow 50% input zero
and span adjustablity within each of the 15 fullscale, input ranges.
Since the unit has 50% adjustability, it can be ranged so
that any 100 volt input span can create the full output (e.g., 25 to 125Vac =
full output).
Unless otherwise specified, the factory presets the Model
G468 as follows:
| Input Range: |
0-500mVAC |
| Output: |
4-20mA |
|
|
The DC power input accepts any DC source between 9 and 30V;
typically a 12V or 24VDC source is used (see Accessories).
Refer to Tables 1 through 3 for the proper switch settings.
With power disconnected, use the switches (9 & 10) on SW1 to select the
input type (voltage or current), on SW2 to select the desired output ranges,
and (1-8) on SW1 to select the desired input range.
Calibration
- After configuring the DIP switches, connect the input to
a calibrated AC source. Connect the output to the device (or a load
approximately equivalent to the device) and apply power. Refer to the Terminal
Wiring Diagram (Figure 2).
- Set the calibrator to the desired minimum and adjust the
zero potentiometer for the desired minimum output.
- Set the calibrator to the desired maximum and adjust the
span potentiometer for the desired maximum output.
- Repeat steps 2 and 3, if necessary for best
accuracy.
|
|