The Ultra SlimPak II is an exciting new line
of isolating signal conditioners from Action Instruments with greater accuracy
and better stability than virtually any other signal conditioners on the market
today.
The WV118 is an RTD Limit Alarm with dual
setpoints and two contact closure outputs. The input type and alarm functions
are field configurable, offering maximum flexibility. The WV118 supports Pt100,
in both 0.00385 and 0.00392 alphas, and Cu10 RTDs. All ranges allow the
setpoints to be fully adjustable throughout the entire range.
The WV118-2000 contains two standard
non-latching SPDT relays. When power is removed, the relays revert to their
non-powered state. The WV118-2001 contains two latching relays. Whatever
position the relays are in when power is removed is where they will remain when
power is re-applied (a reset switch is provided to reset the relays after the
alarm is no longer true). Both models are configurable as a single or dual
setpoint alarm, with HI or LO trips. The WV118-2000 supports failsafe or
non-failsafe operation. In failsafe operation the relay coil is energized when
the process is below the HI setpoint or above the LO setpoint (opposite for
non-failsafe). In the failsafe mode, a power failure results in an alarm state
output.
Operation Each of the alarm setpoints has a
respective HI or LO deadband. Red LEDs will illuminate indicating an alarm
condition. The trip will reset only when the process falls below the HI
deadband or rises above the LO deadband. (The WV118-2001 requires pressing the
reset switch in order to reset the relay after being tripped.) The deadband can
be left at the minimum level (the factory default) or can be set to whatever
level is desired. |