TECHNICAL SPECIFICATION (WV118) |
| Inputs |
Sensor
Types |
|
Pt100 0.00385,
Pt100 0.00392, Cu10 |
| Sensor Connection |
|
2-wire or 3-wire |
| Ranges |
|
|
|
| Pt100 RTDs |
|
|
|
| C |
F |
alpha |
range no. |
| -200 to 60 0 |
-32 to 1112 |
0.00385 |
1 |
| -200 to 260 |
-328 to 500 |
0.00385 |
2 |
| -200 to -100 |
-328 to -148 |
0.00385 |
3 |
| -50 to 100 |
-58 to 212 |
0.00385 |
4 |
| -18 to 300 |
0 to 572 |
0.00385 |
5 |
| -200 to 600 |
-328 to 1112 |
0.00392 |
6 |
| -200 to 260 |
-328 to 500 |
0.00392 |
7 |
| -200 to -100 |
-328 to -148 |
0.00392 |
8 |
| -50 to 100 |
-58 to 122 |
0.00392 |
9 |
| -18 to 300 |
0 to 572 |
0.00392 |
10 |
|
| Cu10 RTDs |
|
|
|
| C |
F |
range no. |
| -200 to 260 |
-328 to 500 |
11 |
| -200 to 100 |
-328 to 212 |
12 |
| -200 to100 |
-328 to -148 |
13 |
| -50 to 100 |
-58 to 212 |
14 |
| -18 to 260 |
0 to 500 |
15 |
|
| RTD Excitation |
Pt100: |
|
0.45mA, max. |
|
Cu10: |
|
5.0mA,
max. |
| Lead Wire
Resistance |
|
40% of the base sensor
resistance maximum or 100 ohms (whichever is less) |
| Lead
Wire Effect |
|
|
Changing
from 0 ohm lead resistance (each lead) to maximum allowed lead resistance:
Error <1% of largest span PT and Cu ranges; -200 to 600°C for Pt and
200 to 260°C for Cu. |
| Pushbutton
Adjustment |
|
Effective zero offset:
>95% |
|
(Inputs >10mV) |
|
Effective
span turn down: >95% |
| Local
Range Selection |
|
By DIP switch |
| Response Time |
Dynamic Deadband: |
|
Relay status will change when
proper setpoint/process condition exists for 100mSec. |
|
Normal Mode: |
|
<250mSec
(analog filtering) |
| Setpoint
Effectivity |
|
Setpoints are adjustable (by
pushbutton) over 100% of the selected input span |
| Repeatability |
|
±0.05% of FS, ±1°C (constant temp) |
| Relay Contacts |
|
|
2 SPDT (2 form C) Relays, 1
relay per setpoint |
| Current rating (general use) |
|
120VAC: 5A;
240VAC: 2A; 28VDC: 5A |
| Material |
|
|
Gold flash over silver
alloy |
| Electrical
Life |
|
|
10^5
operations at rated load |
| Reset Switch |
|
|
For unlatching the relay once
the process is no longer in the alarm state (WV118-2001 only). |
| Stability |
|
|
±100ppm of full scale/°C
(±0.01%/°C) |
| CMRR |
|
|
120dB @ DC, >90dB @ 60Hz,
or better |
| Isolation |
|
|
>1800VDC
or peak AC between input, output and power. |
| ESD Susceptibility |
|
Capable of meeting IEC 801-2
level 3 (8kV) |
| Humidity (non-condensing) |
|
|
|
Operating: |
|
15 to 95% RH (@45°C) |
|
Soak: |
|
90% RH for
24hrs (@60°C) |
| Temperature |
Operating: |
|
0 to 60°C |
|
Storage: |
|
-25 to
+85°C |
| Power |
|
9 to 30VDC, 1.0W typical, 2.0W
max |
| Host
Module Interface |
|
IR link,
same specs as Phase 1 modules |
| Size |
|
DIN rail case refer to
Dimensions drawing |
| Environmental |
Operating Temperature: |
|
0°C to
+60°C (32 to 140°F) |
|
Storage
Temperature: |
|
-25°C to +85°C (-13 to
185°F) |
| Operating Relative Humidity
(non-condensing): |
|
15% to 95%RH
at 45°C |
| Non-operating Relative Humidity: |
|
90%RH at 60°C for 24
hours |
| Agency Approvals (EMC & Safety) |
|
CE: EN61326,
EN61010-1 |
|
|
|
UL and CSA Combined mark |
|
Enhanced
Diagnostics Other than when executing the pushbutton calibration
routine, the LEDs blink under the following conditions: RUN (Green):
- On when unit is powered.
- Flashes at 2Hz when input is under range.
- Flashes at 8Hz when input is over range.
SETPOINT A (Red):
- On when Setpoint A is tripped.
- On when setting Setpoint A.
- Flashes while calibrating the input level.
SETPOINT B (Red):
- On when Setpoint B is tripped.
- On when setting Setpoint B.
- On while calibrating the input level.
An Under range condition exists when the signal is lower
than the operational low value by 5°C. An Over Range condition exists when
the signal is higher than the operational high value by 5°C.
Options C620 Factory
calibration of input range, setpoints, and output relays.
Configuring
Modules Unless otherwise specified, the factory presets the Model
WV118 as follows:
| Input: |
Pt100 |
| Range: |
-200°C to 600°C |
| Output: |
Dual, SPDT |
| Trip: |
A: HI, B: LO |
| Failsafe: |
No |
| Deadband: |
A, B: minimum |
|
|
- For other ranges, refer to the SWITCH SETTINGS table (see
Figure 5). Reconfigure switches S1 and S2 for the desired input type and
range.
- Set position 1 of S2 to ON if a WVC16 will be utilized
and remote calibration capability is desired.
- Set position 2 and 3 of S2 to ON for a Hi trip setpoint
or to OFF for a Low trip setpoint.
- Set position 4 of S2 to ON for failsafe operation (e.g.
alarm trips upon power failure) or OFF for non-failsafe operation (-2000
only).
It is also possible to remotely select the setpoints using
an Ethernet connection and the optional WVC16 WebView Communications Interface
module.
Relay Protection and EMI
Suppression When switching inductive loads, maximum relay life and
transient EMI suppression is achieved using external protection (see Figures 2
& 3). Place all protection devices directly across the load and minimize
all lead lengths. For AC inductive loads, place a properly-rated MOV across the
load in parallel with a series RC snubber. Use a 0.01 to 0.1µF pulse film
capacitor (foil polypropylene recommended) of sufficient voltage, and a 47.,
1/2W carbon resistor. For DC inductive loads, place a diode across the load
(PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode
(the RC snubber is an optional enhancement). |
|
|
WV16 Communications
Interface (Optional) The WVC16 Communications Interface adds
functionality never before found in a signal conditioning system. The WVC16
interfaces with Ultra SlimPak II devices via an internal infrared
communications link (no programming required) and provides the ability to
connect as many as 32 modules to the intranet, allowing the user to view
process data on a near real time basis, perform data logging functions on
specified modules, calibrate the signal conditioners remotely, and view
diagnostic information.
The WVC16 contains a web page server and an e-mail
server. Browsers supported include Internet Explorer 5 or later and Netscape
Navigator 4.7 or later. The user has the ability to have setpoint trip
conditions generate an email message for up to 10 recipients. The module also
contains a countdown timer that can be used to notify when routine maintenance
is required, such as re-calibration. The internal temperature of the module can
also be monitored. All memory to support the signal conditioners
historical data, storage of the web pages and all e-mail messages is contained
in the WVC16.
The WVC16 downloads a JAVA applet to the clients
computer. The applet provides access to the signal conditioners data,
which includes the following:
- Module configuration summary
- Module configuration editing
- Diagnostic/warning status
- Alarm setup & status
- E-mail setup, editing & address book
- Process variable viewing
|
|
 |
 |
|
Calibration The
calibration procedure is contained in the Installation & Calibration
Instructions document, which is available on our website (www.actionio.com).
You can also obtain it by telephoning Action technical support (703-
669-1318).
Note that Custom Calibration (option C620) is
available from the factory (settings MUST be within the units specifications).
For a C620, specify the following:
- RTD type and temperature range.
- Setpoint A trip point and reset point.
- Setpoint B trip point and reset point.
- Failsafe (ON/OFF)
|
|