WV128
Thermocouple Input Limit Alarm


TECHNICAL SPECIFICATION (WV128)
Inputs Thermocouples Supported: B, E, J, K, R, S, T
Ranges:
T/C °C °F
B +75 to 1820 +167 to 3308
E -265 to 1000 -445 to 1832
J -210 to 760 -346 to 1400
K -265 to 1372 -445 to 2502
R -25 to 1760 -13 to 3200
S -25 to 1760 -13 to 3200
T -265 to 390 -445 to 734
Overvoltage: ±10V differential
Common Mode: 1800VDC (Input to Ground)
Limit Differential (deadband) 0.2% to 100% of span. Set by Pushbutton Adjustment.
Response Time Dynamic Deadband: Relay status will change when proper setpoint/process condition exists for 100mSec.
Normal Mode: <250mSec (analog filtering)
Setpoint Effectivity: Setpoints are adjustable (by pushbutton) over 100% of the selected input span.
Repeatability: ±0.05% of FS, ±1°C (constant temp)
Relay Contacts 2 SPDT (2 form C) Relays
1 relay per setpoint
Current rating (general use)
120VAC: 5A; 240VAC: 2A; 28VDC: 5A
Material: Gold flash over silver alloy
Electrical Life: 10^5 operations
Reset Switch For unlatching the relay once the process is no longer in the alarm state. (WV128-2001 only)
Local Range Selection By DIP switch
Stability ±100ppm of FS/°C
CMRR 120dB @ DC, >90dB @ 60Hz, or better
Isolation 1800VDC or peak AC between contacts, input & power.
ESD Susceptibility Capable of meeting IEC 801-2 level 3 (8kV)
Humidity Operating: 15 to 95% RH non-condensing @45°C
Soak: 90% RH non-condensing for 24hrs @60°C
Temperature Operating: 0 to 60°C
Storage: -25 to +85°C
Power 9 to 30VDC
1.2W typ., (3.25W max both relays energized)
Host Module Interface IR link
Wire Terminations Screw terminations for 12-22 AWG
Default Configuration
Size DIN rail case – refer to Dimensions drawing
Environmental Operating Temperature: 0°C to +60°C (32 to 140°F)
Storage Temperature: -25°C to +85°C (-13 to 185°F)
Operating Relative Humidity (non-condensing): 15% to 95% at 45°C
Non-operating Relative Humidity (non-condensing): 90% at 60°C for 24 hours
Agency Approvals CE, EN61326, EN61010-1
(EMC & Safety) UL and CSA Combined mark

Enhanced LED Diagnostics
Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:

RUN (Green):
  • On when unit is powered.
  • Flashes at 2Hz when input is under range.
  • Flashes at 8Hz when input is over range.
SETPOINT A (Red):
  • On when Setpoint A is tripped.
  • On when setting Setpoint A.
  • Flashes while calibrating the input level.
SETPOINT B (Red):
  • On when Setpoint B is tripped.
  • On when setting Setpoint B.
  • On while calibrating the input level.
An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.

Options
C620 Factory calibration of input range, setpoints and output relays.

Configuring Modules
Unless otherwise specified, the factory presets the Model WV128 as follows:

Input: Type J
Output: Dual, SPDT
Trip: A: HI, B: LO
Failsafe: NO
Deadband: A, B: minimum
  1. For other ranges, refer to the SWITCH SETTINGS table (see Figure 6). Reconfigure switches S1 and S2 for the desired input type and range.
  2. Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
  3. Set position 2 and 3 of S1 to ON for a Hi trip setpoint or to OFF for a Low trip setpoint.
  4. Set position 4 of S1 to ON for failsafe operation (e.g. alarm trips upon power failure) or OFF for non-failsafe operation (-2000 only).
It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.

Relay Protection and EMI Suppression
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 & 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly-rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1µF pulse film capacitor (foil polypropylene recommended) of sufficient voltage, and a 47., 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).


WV16 Communications Interface (Optional)
The WVC16 Communications Interface adds functionality never before found in a signal conditioning system. The WVC16 interfaces with Ultra SlimPak II devices via an internal infrared communications link (no programming required) and provides the ability to connect as many as 32 modules to the intranet, allowing the user to view process data on a near real time basis, perform data logging functions on specified modules, calibrate the signal conditioners remotely, and view diagnostic information.

The WVC16 contains a web page server and an e-mail server. Browsers supported include Internet Explorer 5 or later and Netscape Navigator 4.7 or later. The user has the ability to have setpoint trip conditions generate an email message for up to 10 recipients. The module also contains a countdown timer that can be used to notify when routine maintenance is required, such as re-calibration. The internal temperature of the module can also be monitored. All memory to support the signal conditioner’s historical data, storage of the web pages and all e-mail messages is contained in the WVC16.

The WVC16 downloads a JAVA applet to the client’s computer. The applet provides access to the signal conditioner’s data, which includes the following:

  • Module configuration summary
  • Module configuration editing
  • Diagnostic/warning status
  • Alarm setup & status
  • E-mail setup, editing & address book
  • Process variable viewing

Calibration
The calibration procedure is contained in the Installation & Calibration Instructions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (703-669-1318).

Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:

  • Input type.
  • Setpoint A trip point and reset point.
  • Setpoint B trip point and reset point.
  • Failsafe (ON/OFF)