T713
RTD Input Isolating, Field Configurable Two-Wire Transmitter


TECHNICAL SPECIFICATION (T713)
Input Span Range (Min/Max) See Tables 1, 2 (in datasheet)
Excitation Current 1mA, typical
Leadwire Resistance Effect 1% of span error with up to 40 Ohms/lead
Output Span 4-20mA/10-50mA, switch selectable
Minimum Output Current 3.3mA, typical
Maximum Output Current
4-20mA: 24mA, typical
10-50mA: 58mA, typical
Supply Voltage Range
4-20mA: 12 to 80VDC
10-50mA: 12 to 60VDC
Maximum Change in Supply - Voltage Effect
0.05% of span
Maximum Change in Load Effect 0.05% of span
Loop Voltage Drop 12VDC @ 20mA
Linearizing Accuracy
T713-0000: ± 0.1% of standard R/T tables, typical; 0.2% max.
T713-0013: ± 0.21% of standard R/T tables, typical; 0.3% max.
Stability Zero: ± 0.02% of span/°C, typical, or 2mV, whichever is greater
Span: ± 0.01% of span/°C, typical
Overall Accuracy (Includes Linearity, Hysteresis, Stability)
± 0.5% of any adjusted span, max.
Zero and Span Adjustability 80% of any selected range
Repeatability ± 0.05% of span, typical
Response Time 150ms, typical, 400ms max.
Output Ripple 0.1% of span, rms, typical
RFI Effect (5W, 470MHz at 3 Ft.) <1% of span error
Isolation 600V DC maximum, input to output to case
Temperature Range
Operating: -40 to 80°C (-40 to 176°F)
Weight 0.64lbs
Agency Approval FM approved intrinsically safe for hazardous locations, certificate No. J.I. 2M2A5.AX (3611).

Calibration
Input: Range 1
Output: 4-20mA
  1. Open the access lid on the top of the unit (see Top View Diagrams).
  2. Select the output range using switch S4. The CLOSED position selects a 10-50mA output. The OPEN position selects a 4-20mA output.
  3. Select the input range from Table 1 or 2 and configure switches S1 through S4.
  4. Connect the input to a calibrated 3-wire resistance source and monitor the output current (refer to terminal wiring).
  5. Set the calibrator to the desired minimum temperature.
  6. Adjust the coarse zero rotary switch to obtain an output of approximately 4mA or 10mA. Adjust the fine zero for exact calibration. Note that it may be necessary to switch coarse zero up or down one position.
  7. Set the calibrator to the desired maximum temperature and perform similar adjustments using the coarse span switch and fine span potentiometer.

Field Mounting
The T713 is designed for installation in industrial field environments. A sealed, diecast aluminum housing protects against corrosion, moisture, dust and electrical noise such as radio-frequency (RFI) and electromagnetic (EMI) interference. All circuit boards are urethane coated for environmental protection and FM approval.

For protection against extreme moisture, hose directed water (NEMA 4) or hazardous environments, use FieldPak model F713. The F713 2-wire transmitter offers the same wide ranging features of the T713, but includes a rugged EP/NEMA 4 enclosure with standard, 1/2" and 3/4" FPT ports for easy hookup and operation in harsh process environments.