- Home - Site Map - Links - Contact Us - About Us - Get In The Loop Search our site:  

T752
Potentiometer Input Isolating, Field Configurable
Two-Wire Transmitter


TECHNICAL SPECIFICATION (T752)
Input Span Range
Max: 0 to 100% of potentiometer
Min: 0 to 20% of potentiometer
Excitation Voltage 50mV typical
Potentiometer Resistance (End to End) 50 Ohms to 200k Ohms
Leadwire Resistance Effect <0.25 uV/Ohm
Input Impedance 5M Ohms, typical
Output Span 4-20mA or 10-50mA, switch selectable
Minimum Output Current 3.3mA typical
Maximum Output Current
4-20mA: 24mA typical
10-50mA: 58mA typical
Supply-Voltage Range
4-20mA: 12 to 80VDC
10-50mA: 12 to 60VDC
Maximum Change in Supply Voltage Effect    0.05% of span
Maximum Change in Load Effect 0.05% of span
Loop Voltage Drop 12VDC @ 20mA
Stability Zero: ±0.02% of span/°C typical,
or 2uV, whichever is greater
Span: ±0.01% of span/°C typical
Overall Accuracy (Includes Linearity,Hysteresis, Repeatability)
±0.05% of any adjusted span maximum
Zero and Span Adjustability 80% of input
Repeatability ±0.05% of span
Response Time 50ms, max.
Output Ripple 0.1% of span rms, typical
RFI Effect (5W, 470MHz at 3 Ft.) <1% of span error
Isolation 600V DC maximum, input to output to case
Temperature Range
Operating: -40 to 80°C (-40 to 176F)
Weight 0.62lbs
Agency Approval FM approved intrinsically safe for hazardous location, certificate No. J.I. 2M2A5.AX.

Calibration
Input Range: 0-100%
Output Range: 4-20mA
  1. Open the access lid on the top of the unit (see Top View Diagram).
  2. Select the output range using switch 1. The CLOSED position selects a 10-50mA output. The OPEN position selects a 4-20mA output. (Switches 2-6 are not used.)
  3. Connect the input to a potentiometer. Connect the output loop to a voltage supply and monitor the output current (refer to the terminal wiring).
  4. Set the potentiometer to the desired minimum.
  5. Adjust the coarse zero rotary switch to obtain an output of either 4mA or 10mA. Adjust the fine zero for exact calibration. Note that it may be necessary to switch the coarse zero up or down one position.
  6. Set the potentiometer to the desired maximum and perform similar adjustments using the coarse and fine span potentiometer.

It may be necessary to repeat steps 4, 5, and 6 for best accuracy.

Field Mounting
The T752 is designed for installation in industrial field environments. A sealed, diecast aluminum housing protects against corrosion, moisture, dust and electrical noise such as radio-frequency (RFI) and electromagnetic (EMI) interference. All circuit boards are urethane coated for environmental protection and FM approval.

For protection against extreme moisture, hosedirected water (NEMA 4) or hazardous environments, use Action’s T805 explosion-proof housing. The T805 provides a 1/2" and 3/4" FPT port for easy hook-up and operation in harsh process environments. Model T805 is FM and CSA certified for use in Class I, Groups B, C & D and Class II, Groups E, F & G hazardous locations.