T761
AC Input Isolating Field Configurable
Two-Wire Transmitter


TECHNICAL SPECIFICATION (T761)
Input Span Range (Max/Min) See table 1 (in datasheet)
Leadwire Resistance Effect <0.25 uV/Ohm
Input Impedance
Ranges 1-8: >1M Ohm
Ranges 9-12: 0.5 Ohm shunt
Output Span 4-20mA/10-50mA, switch selectable
Minimum Output Current 3.3mA, typical
Maximum Output Current
4-20mA: 24mA, typical
10-50mA: 58mA, typical
Supply-Voltage Range
4-20mA: 12 to 80VDC
10-50mA: 12 to 60VDC
Maximum Change in supply Voltage Effect 0.05% of span
Maximum Change in Load Effect 0.05% of span
Loop Voltage Drop 12VDC @ 20mA
Stability Zero: ±0.02% of span/°C, typical, or 10uV/°C, whichever is greater
Span: ±0.02% of span/°C, typical
Overall Accuracy (Includes Linearity,Hysteresis and Stability)
±0.5% of any adjusted span (50-400Hz sine wave input), max.
Frequency Response (±0.5dB) 20Hz to 3KHz; average reading calibrated to sine wave input
Maximum DC Input Component 50% of range
Zero and Span Adjustability 80% of any selected range
Repeatability ±0.05% of span, typical
Response Time 500ms, typical
Output Ripple 0.5% of span, rms, typical
RFI Effect (5W, 470MHz at 3 Ft.) <1% of span error
Isolation 600V DC maximum, input to output
Temperature Range
Operating: -40 to 80°C (-40 to 176°F)
Weight 0.64lbs

Calibration
  1. Open the access lid on the top of the unit (see Top View Diagram).
  2. Select the output range using switch S1. The CLOSED position selects a 10-50mA output. The OPEN position selects a 4- 20mA output.
  3. Select the input range from Table 1 and configure switches S2 through S6.
  4. Connect the input to a calibrated AC voltage or current source. Connect the output loop to a voltage supply and monitor the output current (refer to terminal wiring).
  5. Set the calibrator to the desired minimum.
  6. Adjust the coarse zero rotary switch to either 4mA or 10mA. Adjust the fine zero for exact calibration. Note that it may be necessary to switch coarse zero up or down one position.
  7. Set the calibrator to the desired maximum and adjust the fine span to obtain an output of either 20mA or 50mA. Repeat steps 5-7, if necessary for best accuracy.

Field Mounting
The T761 is designed for installation in industrial field environments. A sealed, diecast aluminum housing protects against corrosion, moisture, dust and electrical noise such as radio-frequency (RFI) and electromagnetic (EMI) interference.

For protection against extreme moisture, hosedirected water (NEMA 4) or hazardous environments, use the T805 explosion-proof housing. The T805 provides a 1/2" and 3/4" FPT port for operation in harsh process environments. The T805 is FM and CSA certified for use in Class I, Groups B, C & D and Class II, Groups E, F & G hazardous locations.